ACK2
OIL/GAS FIRED HOT WATER BOILERS
ACK2-80 ....... ACK2-3000
INSTALLATION, AND COMMISIONING MANUAL
Rev B : Feb.2005
05 001 GB
Distribuitor: CALOR SRL
Str. Progresului nr. 30-40, sector 5, Bucuresti
tel: 021.411.44.44, fax: 021.411.36.14
www.calorserv.ro - www.calor.ro
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - Distribuitor: CALOR SRL

ACK2 OIL/GAS FIRED HOT WATER BOILERS ACK2-80 ... ACK2-3000 INSTALLATION, AND COMMISIONING MANUAL Rev B : Feb.2005 05 001 GB Distr

Page 2

- 9 - Protection against exceeding the maximum operating pressure; Each boiler shall be served by at least one safety valve in order to protect th

Page 3 - 2 WARNINGS

- 10 - Devices for controlling the operation temperature to adapt the heat supply to the heat demand. The maximum set-point of the temperature cont

Page 4

- 11 - Operational requirements of open vented systems; In order to maintain a safe and economical operation, open vented heating systems shall be e

Page 5 - 4 GUARANTEE AND SERVICE

- 12 - 8.4 FLUE GAS EXHAUST SYSTEM. ACK2 boilers are B23 type appliance so the flue gases must be connected to an adequate draught chimney, withou

Page 6 - 6 OPERATING PRINCIPLES

- 13 - Note :During boiler economic life, the total make up water volume can not be more then 3 times of the total system water. Guarantee will not

Page 7 - 7 MAIN PARTS

- 14 - Before firing the burner, be sure that system is full of water and all control items are set to desired value and working properly. Check the

Page 9 - SAFETY ARRANGEMENTS

16 PI SPL2 TCL TC TI PI LV PI SPL1 ACP SP V HS MET HS ACP MET 3W V 3W V PR SP TCL TC TI PI LV SPL2 SPL1 FT SV SV FT Heating system Circulation pump

Page 10

17 FOR OPEN VENTED (OPEN EXPANSION CISTERN) SYSTEMSTYPICAL SAFETY EQUIPMENT AND HYDROULIC ARRANGEMENTTCLTCLockable valveValveVLVBOILERDVARFSVPRCVVVTI

Page 11 - SYTEMS

18 100100BOILER FEET WIDTHBOILER FEET LENGHT80 80150- BOILER FOUNDATION SHALL BE ENOUGH STRENGHT TO CARRY THE BOILER FULL WITH WATER AND ACCESSORIES

Page 12

- 1 - INDEX 1 INTRODUCTION ……………………………………………………… 2 2 WARNINGS …..……………………………….…………………….…. 2 3 DECLARATION OF CONFORMITY …………………………..…….

Page 13

19 ABW W W They can be changed according to local standarts.Note : These dimensions are recomendations only.H : Height of the boiler room must

Page 14 - 9 START UP

20 35150012520010704050601009080NOMINAL OUTPUT (kW)45025015020022517530035040080090050060070010001250180105 15 20 25 30160200220FOR CIRCULAR CROSS S

Page 16 - 10 ANEX

22 14x143515003020108050407060100901255 10 15 20 25 30FOR SQUARE CROSS SECTIONS (PLEWA)600NOMINAL OUTPUT (kW)3002251752002504504003505001250900800700

Page 17

23 ACK2 OIL/GAS FIRED HOT WATER BOILERS ALARKO - GAS BURNER SELECTION CHART Boiler Net Heat Gross Heat Back pressure Burner typ

Page 18

24 ACK2 OIL/GAS FIRED HOT WATER BOILERS LAMBORGHINI - GAS BURNER SELECTION CHART Boiler Net Heat Gross Heat Back pressure Burner

Page 19 - - BOILER FOUNDATION

25 ACK2 OIL/GAS FIRED HOT WATER BOILERS ALARKO - OIL BURNER SELECTION CHART Boiler Net Heat Gross Heat Back pressure Burner typ

Page 20 - BOILER ROOM LAYOUT

26 ACK2 OIL/GAS FIRED HOT WATER BOILERS CIB UNIGAZ - GAS BURNER SELECTION CHART Boiler Net Heat Gross Heat Back pressure Burner

Page 21 - EFFECTIVE CHIMNEY HEIGHT (m)

27 ACK2 OIL/GAS FIRED HOT WATER BOILERS CIB UNIGAZ - OIL BURNER SELECTION CHART Boiler Net Heat Gross Heat Back pressure Burner

Page 22

TECHNICAL SPECIFICATIONS OF ACK2 TYPE BOILERS Range of Temperature Control °C 55-90 Boiler Type Hot Water, Two Pass, Reversal Flame, Ste

Page 23 - NOMINAL OUTPUT (kW)

- 2 - 1 INTRODUCTION This manual comprises the information concerning the Installation, operation, use and maintenance of ACK2 hot water boilers.

Page 24

- 29 - BOILER CONTROL PANELS Boiler Control Panel Device Functions : 1. Main switch : Energize or shut off the panel 2. Saf

Page 25

- 30 - BOILER CONTROL PANEL WIRING DIAGRAMS SAFETY CONTROLSRT2 : NO220/230 V (AC)50 Hz - 16 A (max)FNBURNERLG : PANEL EARTHINGEL :

Page 26 - ALARKO - OIL

- 31 - NNBURNER50 Hz - 16 A (max)220/230 V (AC)FF : FUSEC : COMMONMS : MAIN SWITCH (ON/OFF)LT : SAFETY LIMIT THERMOSTATBOILER CONTROL PANELTWO

Page 27

- 3 -  Boilers must not be installed in areas where inflammable vapors and materials are likely to e present. To avoid damage to the boilers, con

Page 28

- 4 - 3 DECLARATION OF CONFORMITY We hereby make the fallowing declaration with regard to the appliance trademark ACK2, models ACK2-80, ACK2-100,

Page 29

- 5 - 5 GENERAL SPECIFICATIONS  ACK2 boilers are reverse flame, 2 pass, wet back, cylindrical shell type, hot water, liquid or gas fired, B2

Page 30

- 6 - 7 MAIN PARTS 1- Combustion chamber. 2- Second pass combustion pipes and turbulators. 3- Main boiler body. 4- Two way hi

Page 31 - 50 Hz - 16 A (max)

- 7 - 8 INSTALLATION The installation of the boilers must be performed according to the current local standards and in addition, instructions sta

Page 32

- 8 -  All electrical connections must be according to current standards and wiring diagrams are given in this manual. Please pay special attention